With glass fiber as reinforcement material and resin as matrix material, the double walled oil tank is formed by making a layer of impermeable shell outside the single-layer steel tank through the spray process and contact forming process.
Scope of Production
Diameter ≤ 4m; capacity ≤ 100m3
Can be designed and produced according to customer's demands.
Product Standard
SH/T 3178-2015 The Technical Specification of Buried SF Double Walled Tank Used for Gas Station
Applications
Gas station product oil and chemical plant hazardous chemical storage areas.
Product Characteristics
Environmental protection and anti-seepage, no pollution; Corrosion resistance, long service life; Light weight, convenient construction and installation.
SF Table of design parameters for SF double walled tanks
Volume |
Diameter |
Length |
Shell thickness |
Head thickness |
Thickness of outer layer |
m³ |
mm |
mm |
mm |
mm |
mm |
10 |
1900 |
3916 |
≥6 |
≥7 |
≥4 |
20 |
2400 |
4840 |
≥6 |
≥7 |
≥4 |
2600 |
4600 |
≥7 |
≥8 |
≥4 |
30 |
2400 |
7100 |
≥6 |
≥7 |
≥4 |
2600 |
6250 |
≥7 |
≥28 |
≥4 |
40 |
2400 |
9300 |
≥6 |
≥7 |
≥4 |
2600 |
8050 |
≥7 |
≥8 |
≥4 |
50 |
2400 |
11560 |
≥7 |
28 |
≥4 |
2600 |
10080 |
≥7 |
≥28 |
≥4 |
Note: the above specification parameters are for reference only, and can be customized according to customer's requirements.